Top Industrial Automation and Electrical Instrument from HKXYTECH
  • Chlorine Analyzers FC500G

Chlorine Analyzers FC500G

2016-05-26 16:14:54

Description:

FC500G non-reagent free available chlorine analyzer adopts the polarographic method, using a rotating electrode to continuously measure online the concentration of free available chlorine. The FC500G is intended for measurements in the water distribution network, at pumping stations, water delivery points, schools, and public facilities.……

New Products

G.M. International X1-IS-AO-02-S I.S. SIL2 HART® Isolating Driver module

G.M. International X1-IS-AO-02-S I.S. SIL2 HART® Isolating Driver module. GMI Intrinsically Safe Isolators, Analog Output

G.M. International D1020S SIL 2 Powered Isolating Driver

G.M. International D1020S SIL 2 Powered Isolating Driver Smart-HART® compatible DIN-Rail. GMI Intrinsically Safe Isolators

G.M. International D1020D SIL 2 Powered Isolating Driver

G.M. International D1020D SIL 2 Powered Isolating Driver Smart-HART® compatible DIN-Rail. GMI Intrinsically Safe Isolators

G.M. International X1-IS-AO-01-S I.S. SIL3 HART® Isolating Driver module

G.M. International X1-IS-AO-01-S I.S. SIL3 HART® Isolating Driver module. GMI Intrinsically Safe Isolators, Analog Output

Assortments

Description

FC500G

FC500G non-reagent free available chlorine analyzer adopts the polarographic method, using a rotating electrode to continuously measure online the concentration of free available chlorine.

The FC500G is intended for measurements in the water distribution network, at pumping stations, water delivery points, schools, and public facilities.

Features

  • Measuring range can be selected from 0 to 1/0 to 2/0 to 3mg/l and 0 to 5/0 to 10 mg/l.

  • Rotating electrode/ceramic bead cleaning has been improved to making cleaning automatic and continuous.

  • Easy-to-maintain (-clean) cell construction.

Specifications

Measured ObjectFree chlorine in tap water
Measuring SystemPolarographic method using rotating electrode
Measuring RangeAny of 0 to 1/0 to 2/0 to 3 mg/l and 0 to 5/0 to 10 mg/l certainly, use to air purge
Output Signal4 to 20mA DC (load resistance: Maximum 550 Ω)
Sample Solution ConditionTemperature: 0 to 40℃
pH: 6.5 to 7.5
Flow Rate: 0.1 to 2.5 l/min (at cell inlet)
Pressure: 1 to 30 kPa (without VALVE)
              1 to 150 kPa (with VALVE)
Conductivity: 100 to 300 μS/cm
SS (Suspended Solid): 10 mg/l or less
ElectrodeIndicating electrode: Rotating gold electrode
Reference electrode: Silver electrode (with Pt1000 RTD installed)
Electrode CleaningCeramic bead cleaning
Ambient Temperature-10 to 50℃
InstallationIndoor
Power Supply100 V AC/110 V AC / 200 V AC/220 V AC ±10 %, 50/60 Hz
WeightApprox. 6.5 kg

Performance

Linearity±5 % of full scale
Repeatability2 % of full scale
StabilityZero drift; ±1 % of full scale/month or less
Span drift; -10 % of full scale/month or less
Response timeApprox. 2 min (90 % response time)