Top Industrial Automation and Electrical Instrument from HKXYTECH
  • Yokogawa Metal Variable Area Meter RAKD

Yokogawa Metal Variable Area Meter RAKD

2015-06-29 16:39:24

Description:

Features - Easy-to-read-display - All stainless steel design - Suitable for applications according to IEC 61508 and ISO 13849 - Adjustment valve and flow controller available - Fast connection technique using Quickon connector - Intrinsically safe outputs - Special material like Monel and Hastelloy on request……

New Products

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature New load group, width: 22.5 mm.

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature Width: 22.5 mm.

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA, carrier module 8-fold carrier for holding 8 I/O modules of the ET 200SP HA.

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA, carrier module 2-fold carrier for holding 2 I/O modules of the ET 200SP HA.

Assortments

Description



The small metal Rotameter RAKD differentiates itself from other comparable variable area meters by means of light and guided float design offering the smallest measurable flow ranges in the market. RAKD meters can be fitted with a fine control valve and are designed with horizontal process connections. An integrated flow controller based on the differential pressure principle, which allows a constant flow rate to be maintained regardless of any variations in process pressure, is just one of the many different options available. The RAKD with either standard or fail safe limit switches is suitable for safety applications up to SIL level 2. The configuration with valve and controller reaches SIL level 1. The RAKD Rotameter combines several benefits of the float principle: a robust design, reliable measurements, independence of the electrical power supply when operated as mechanical pointer instruments and an electrical output signal. They are moreover easy to install and require no maintenance. Both the RAMC and the RAKD are packaged in an attractive, all-stainless steel housing and boast a long service life under the harshest industrial conditions.   RAKD General Specifications  RAKD User's Manual Terms of Use for ManualsList of Rotameter General SpecificationsList of Rotameter User's Manual 

Features

Easy-to-read-display
All stainless steel design
Suitable for applications according to IEC 61508 and ISO 13849
Adjustment valve and flow controller available
Fast connection technique using Quickon connector
Intrinsically safe outputs
Special material like Monel and Hastelloy on request

Specifications



For Pipe SizesDN 15 to DN 150 (1/2” – 6“)
Process ConnectionsFlange, threaded or Triclamp
Measuring RangeWater 20 °C: 0,1 l/h to 250 l/h
Air 20 °C 1 bar abs.: 4 l/h to 8000 l/h
Wetted Parts Material1.4571 (AISI 316Ti) Hastelloy,
Monel and Titanium on request
Process Temperature-25 °C to + 250 °C
Process Pressure100 bar, higher pressures on request
Ambient Temperature-25 °C to 100 °C
Accuracy acc. VDE/VDI 3513-2(qG =50%)4 %
Ex-approvalsATEX, NEPSI, FM, CSA
Signal OutputsAnalog 4-20mA, pulse output
Power Supply24 V DC 2-wire
Degree of ProtectionIP66/IP67
Suitable for Applications acc. IEC 61508
and Machinery Directive ISO 13849
Yes
Additional FeaturesLimit switches for low/high alarms
Fine control valves
Pressure controller
Easy installation with Quickon connector