Description:

3 wire, 4-20mA and RS485 MODBUS output fixed point detector with in-built alarm and fault relays for the protection of personnel and plant from toxic and oxygen hazards.……

New Products

FXT1-P37 Right Angle Milling Head

FXT1-P37 Right Angle Milling Head - HKXYTECH

FXT1-P24 Right Angle Milling Head

FXT1-P24 Right Angle Milling Head - HKXYTECH

FXT1-P18 Right Angle Milling Head

FXT1-P18 Right Angle Milling Head - HKXYTECH

FXT1-AC Fully Automatic Right Angle Milling Heads

FXT1-AC Fully Automatic Right Angle Milling Heads - HKXYTECH

Assortments

Description

Honeywell Analytics Sensepoint XCD RTD Remote toxic and oxygen gas detector for industrial applications Explosion-Proof Transmitters Industrial Gas Systems

 

Use

3 wire, 4-20mA and RS485 MODBUS output   fixed point detector with in-built alarm and fault relays for the protection   of personnel and plant from toxic and oxygen hazards.

Incorporating a transmitter with local   display and optional remote mounted sensor, fully configurable via   non-intrusive magnetic switch interface with a wide range integral and

remote sensors available.

Electrical

Input   Voltage Range

16 to 32VDC (24VDC nominal)

Max   Power Consumption

Maximum power consumption is dependent on   the type of gas sensor being used. Electrochemical cells = 3.7W

Maximum inrush current = 800mA at 24VDC

Current   Output

Sink or source

Relays

3 x 5A@250VAC. Selectable normally open   or normally closed (switch) and energized/de-energised (programmable)

Alarm relays default normally   open/de-energized. Fault relay default normally open/energized

Communication

RS485

Construction

Material

Housing: Epoxy painted aluminium alloy   LM25 or 316 stainless steel

Sensor: Polyphenylene sulfide (PPS) (see   Sensepoint specifications)

Weight   (approx)

Aluminium Alloy LM25: 4.4lbs

316 Stainless Steel: 11lbs

Mounting

Integral mounting plate with 4 x mounting   holes suitable for M8 bolts. Optional pipe mounting kit for horizontal or   vertical pipe Ø1.5 to 3" (2" nominal)

Cable   Entries

2 x ¾”NPT conduit entries. Suitable   blanking plug supplied for use if only 1 entry used. Seal to maintain IP   rating

Environmental

IP   Rating

IP67 in accordance with EN60529:1992

Certified   Temperature Range

40ºF to +149ºF (-40ºC to +65ºC)

Certification

US,   Latin America, Canada

cCSAus Ex d IIB+H2; Class I, Zone 1, AEx   d IIB+H2; Class I, Division 2, Groups B, C & D

Class I, Zone 1, AEx d ia IIC Gb; Class   I, Div. 2, Groups B, C and D

Inmetro Ex d IIC T6 Gb, Ex tb IIIC T85ºC   Db, IP66, -40ºC < ta < +65ºC

EMC

CE: EN50270:2006 EN6100-6-4:2007, Ex d   IIC T6 Gb, Ex tb IIIC T85ºC Db, IP66, -40ºC < ta < +65º C

Standards

CAN/CSA-C22.2 No. 0-M91, CAN/CSA-C22.2   No. 60079-0:07, CAN/CSA-E60079-11:02, CAN/CSA-C22.2 No. 60079-1:07, ANSI/UL   60079-11:09, ANSI/UL 60079-1:09,

C22.2 No. 142-M1987, C22.2 No. 213-M1987,   UL 508 17th Ed., ANSI/ISA -12.12.01-2010 ABNT NBR IEC 60079-0:2008, ABNT NBR   IEC 60079-1:2009, IEC 60079-

31:2008 e ABNTNBR IEC 60529:2009.

 

If you have any question, please do not hesitate to contact with me online

Contact details :

Shirley Sun

Sales Engineer

HONGKONG XIEYUAN TECH CO., LIMITED

Add : 7-A16, Caishen Commercial Plaza, Hankou Railway Station, Wuhan, China

M : +86-15172506760 (WhatsApp & Wechat) | T : +86-27-85309780  | F : +86-27-85309780

Email : Shirley@whxyauto.com     Skype : 169649423@qq.com

Web : www.hkxytech.com