Top Industrial Automation and Electrical Instrument from HKXYTECH
  • Yokogawa AAI135-S00 Current Input Module and Current I/O Module Isolated Channels

Yokogawa AAI135-S00 Current Input Module and Current I/O Module Isolated Channels

2018-12-27 17:30:00

Description:

AAI135-S00……

New Products

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature New load group, width: 22.5 mm.

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature Width: 22.5 mm.

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA, carrier module 8-fold carrier for holding 8 I/O modules of the ET 200SP HA.

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA, carrier module 2-fold carrier for holding 2 I/O modules of the ET 200SP HA.

Assortments

Description

Yokogawa AAI135-S00 Current Input Module and Current I/O Module Isolated Channels

 

Items

Specifications

Model

AAI135 (*1)

Number of I/O channels

8-channel input, isolated channels

I/O signal

4 to 20 mA

Allowable input current

25 mA

Withstanding voltage

Between input and system:

 500 V AC, for 1 minute

Between input channels:

 500 V AC, for 1 minute (*2)

Input

resistance

Power ON

290 Ω (at 20 mA) to 450 Ω (at 4 mA) (*3)

Power OFF

500 kΩ or larger

Allowable load resistance


Circuit-open detection


Accuracy

±16 µA

Data update period

10 ms

Transmitter power supply

15.0 V or higher (at 20 mA)

29.3 V or less (at 0 mA) (*5)

Temperature drift

±16 µA/10 °C

Maximum current

consumption

360 mA (5 V DC), 450 mA (24 V DC)

Weight

0.3 kg

External connection

Pressure clamp terminal, MIL connector   cable, dedicated cable (KS1)

HART communication (*6)

Available

*1: A Zener barrier is not allowed to be connected with this module. Use an isolation barrier when the module is used in

intrinsically safe applications.

*2: When the ML connector cable is used, the withstanding voltage depends on the electrical specifications of the cable.

*3: The module input resistance viewed from the terminals depends on the current strength as calculated as below:

250 Ω + voltage drop in the input protection circuit/current value

F06E.ai

*5: This voltage is generated between the connecting terminals for 2-wire transmitters for this module. When calculating the

minimum operating voltage for transmitters, consider to allow margins for voltage drop in external wiring.

*6: When this module is installed to a ER bus node unit with HART function, the EB401 firmware must be rev. 2 or later.

 

Similar model codes for your reference :

AAI135-S00, AAI135-S50, AAI141-H00, AAI141-H53, AAI141-S00, AAI141-S03, AAI141-S50, AAI143-H00, AAI143-H50, AAI143-HE3, AAI143-S50, AAI143-S51, AAI543-H00, AAI543-H03, AAI543-H50, AAI543-H53, AAI543-H60, AAI543-S00, AAI543-S50, AAI841, AAI841-H50, AAI841-S00

 

If you have any question, please do not hesitate to contact with me online

Contact details :

Shirley Sun

Sales Engineer

HONGKONG XIEYUAN TECH CO., LIMITED

Add : 7-A16, Caishen Commercial Plaza, Hankou Railway Station, Wuhan, China

M : +86-15172506760 (WhatsApp & Wechat) | T : +86-27-85309780  | F : +86-27-85309780

Email : Shirley@whxyauto.com     Skype : 169649423@qq.com