Top Industrial Automation and Electrical Instrument from HKXYTECH
  • YOKOGAWA ESD SAT145 TC/mV Input Module

YOKOGAWA ESD SAT145 TC/mV Input Module

2016-06-15 00:14:23

Description:

SAI143 SAV144 SAI533 SAT145 SDV144 SDV531 SDV541 SDV521 SDV526 Our Products covers ESD (Emergency Shut Down), F&G or FGS (Fire and Gas Systems), BMS (Burner or Boiler Management Systems) as well as HIPPS or HIPS (High Integrity (Pipeline) Protection Systems)..……

I/O Module Place of Origin: Japan,Yokogawa original packing, by carton

New Products

Orbinox VG SERIES 61 Slurry knife gate valve

Orbinox SERIES 61 (VG) model knife gate valve is a wafer type valve equipped with two metal reinforced rubber sleeves,designed for applications with abrasive slurries.

Crosby J-Series Direct Spring Pressure Relief Valves

J-Series valves provide high quality and dependable overpressure protection for air, gas, steam, vapor, liquid and two-phase applications in one simple design. Now available with two new to the world technologies, Balanced Diaphragm and Bellows Leak Detection.

Vanessa Series 30,000 Cryogenic Triple Offset Valve

The Vanessa Series 30,000 Cryogenic Triple Offset Valve is a virtually maintenance-free valve with tightness, operability and torque demand unaffected by cryogenic conditions and severe temperature fluctuations.

Sempell Model SOT High pressure steam safety valve

The Sempell Model SOT is a high-pressure steam safety valve designed for boiler protection and steam system safety.

Assortments

Description

YOKOGAWA ESD Analog Input Module SAI144 Series

 

STANDARD SPECICATIONS

 

 

TC/mV Input Module

 

This module receives signals from mV and thermocouple (TC). The SAT145 can be made dual redundant.


Item




Specifications


Model


SAT145





Number of input channels

16-channel, Isolated Channels




TC: JIS C 1602, IEC 60584-1 (ITS-90)




J: -210 to 1200 °C

K: -270 to 1372 °C




E: -270 to 1000 °C

T: -270 to 400 °C


Input signal

S: -50 to 1767 °C

R: -50 to 1767 °C




N: -270 to 1300 °C

B: 42 to 1820 °C




mV







-100 to 150 mV, -20 to 80 mV, -5 to 25 mV





Switching input signals

TC/mV can be set individually for CH1 to CH16.


Permissible input range

± 5 V





Withstand voltage (*1)

Between input and system: 1500 V AC for 1 minute


Between channels: 200 V AC for 1 minute









Input impedance

At least 1 MΩ during Power-ON


At least 1 MΩ during Power-OFF











Accuracy

TC

± 40 μV



mV

± 40 μV













Allowable total resistance of signal

1000 Ω or less



source plus wiring








Effect of allowable signal source

± 20 μV (*2)




resistance (1000 Ω)









Reference junction compensation

-20 to 0 °C

± 1.5 °C



0 to 30 °C


± 1.0 °C



accuracy (*3) (*4)




30 to 70 °C

± 1.5 °C











Temperature drift

± 40 μV / 10 °C



Data update period

150 ms





Burn-out


Individual channel setting



Setting: Burnout upscale/Burnout downscale




Detection time: 1.5 s








Ambient temperature (during operation)

-20 to 70 °C




Maximum current consumption

5 V system: 400 mA



24 V system: 200 mA












Weight


Approx. 0.47 kg



External connection

Dedicated signal cable (AKB331)


 

YOKOGAWA ESD Analog Input Module SAT145

 

 MODEL AND SUFFIX CODES

 



Description

Model

SAT145

TC/mV Input Module (16-channel, Isolated Channels)

 

 

Suffix Codes

-S

Standard type

     6

With signal cable interface adapter and no explosion protection

     F

With signal cable interface adapter and explosion protection

        3

With ISA Standard G3 and temperature (-20 to 70 ºC)

Option Codes

/PRP

With prevention pin of false insertion

 

 

ORDERING INFORMATION

Specify the model and suffix codes.

For selecting the right products for explosion protection, please refer to TI 32S01J30-01E without fail.

 

 

SAT145 TC/mV Input Module (16-channel, Isolated Channels)

SAT145-S63 ,SAT145-S63/PRP, SAT145-SF3/PRP

 

YOKOGAWA ESD Analog Input Module SAT145