YOKOGAWA ESD Analog Input Module SAI143-H53/A4S00
2016-06-14 00:04:17
Description:
YOKOGAWA ESD SAI143-H53 This GS describes the hardware specifications of the analog I/O modules that can be mounted on the safety node unit and the safety control unit.……
YOKOGAWA ESD SAI143-S53 Place of Origin: Singapore,Yokogawa original packing, by carton
New Products
FXT1-P37 Right Angle Milling Head
FXT1-P37 Right Angle Milling Head - HKXYTECH
FXT1-P24 Right Angle Milling Head
FXT1-P24 Right Angle Milling Head - HKXYTECH
FXT1-P18 Right Angle Milling Head
FXT1-P18 Right Angle Milling Head - HKXYTECH
FXT1-AC Fully Automatic Right Angle Milling Heads
FXT1-AC Fully Automatic Right Angle Milling Heads - HKXYTECH
Assortments
▶ Pressure Transmitter EJA
▶ Pressure Transmitters EJA-E
▶ Pressue Transmitter EJX
▶ Safety Instrumented System (SIS)
▶ Valve Positioners & Converters
▶ Field Mount Indicators
▶ Temperature Transmitters
▶ Magnetic Flowmeters
▶ Vortex Flowmeter
▶ Ultrasonic Flowmeters
▶ Coriolis Mass Flowmeters - ROTAMASS 3-Series
▶ Variable Area Flowmeters – Rotameters
▶ Device Smart Communicators
▶ PORTABLE AND HANDHELD INSTRUMENTS
▶ Distributed Control System (DCS)
▶ Process Analyzers
▶ Paperless Recorders
▶ Strip Chart Recorders
▶ Data Acquisition Equipment
▶ UT Series Temperature Controllers
▶ UP Series Program Controllers
▶ UM Series Digital Indicators with Alarms
▶ UT100 Series Temperature Controllers
▶ UD Series Manual Setters
▶ Limit Controllers
▶ YS Series Single-loop Controllers
Description
YOKOGAWA ESD Analog Input Module SAI143-H53
n STANDARD SPECIFICATIONS
l Current Input Module
This module inputs 4 to 20 mA signals from the field.
The SAI143 can be made dual redundant.
Item | Specifications | ||
Model | SAI143 (*1) | ||
Number of input channels | 16-channel, module isolation (*5) | ||
Rated input range | 4 to 20 mA | ||
Permissible input range | 0 to 25 mA | ||
Input impedance during Power-ON | 250 Ω+ Voltage drop in the input protection circuit inside the module | (*6) | |
Current value | |||
Input impedance during Power-OFF | 500 kΩ minimum | ||
Rated accuracy | SAI143-S : ±16 µA (Input range 1 to 23 mA) | ||
SAI143-H : ±16 µA (Input range 0.05 to 23 mA) (*3) (*4) | |||
Data update frequency | 40 ms | ||
Temperature drift | ±16 µA/10 °C | ||
Transmitter power supply | 16.15 V minimum (at 20 mA) | ||
26.4 V maximum (at 0 mA) | |||
(Output current limit: 25 mA) | |||
2/4-wire setting | Individual channel setting | ||
Changed by setting pins | |||
Withstand voltage | 1.5 kV AC between input signal and system for 1 minute (*2) | ||
Maximum current consumption | 5 V system: 320 mA, | ||
24 V system: 550 mA | |||
Weight | Approx. 0.34 kg (For pressure clamp terminal block or MIL cable) | ||
Approx. 0.39 kg (With signal cable interface adapter) | |||
External connection | Pressure clamp terminal | ||
MIL cable | |||
Dedicated signal cable | |||
Support PRM | Available (SAI143-H) |
YOKOGAWA ESD Analog Input Module SAI143-H53
n MODEL AND SUFFIX CODES
Description | ||
Model | SAI143 | Analog Input Module (4 to 20 mA, 16-channel, module isolation) |
Suffix Codes | -S | Standard type |
-H | With HART communication [Release: R1.02.00] (*1) | |
5 | For pressure clamp terminal block or MIL cable with no explosion protection | |
6 | With signal cable interface adapter and no explosion protection (*2) | |
E | For pressure clamp terminal block or MIL cable with explosion protection | |
F | With signal cable interface adapter and explosion protection (*2) | |
3 | With ISA Standard G3 and temperature (-20 to 70 ºC) | |
C | With ISA Standard G3 and high-density installation (-20 to 70 ºC) (*5) | |
Option Codes |
/A4S00 | With pressure clamp terminal block for analog [Model: STA4S-00] |
/A4S10 | With pressure clamp terminal block for analog (with surge absorber) [Model: STA4S-10] | |
/A4D00 | With dual-redundant pressure clamp terminal block for analog (*3) [Model: STA4D-00] | |
/A4D10 | With dual-redundant pressure clamp terminal block for analog (with surge absorber) (*3) [Part name: STA4D-10] | |
/PRP | With prevention pin of false insertion (*4) | |
/CCC01 | With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01] |
n ORDERING INFORMATION
Specify the model and suffix codes.
For selecting the right products for explosion protection, please refer to TI 32S01J30-01E without fail.
SAI143 Analog Input Module (4 to 20 mA, 16-channel, module isolation)
SAI143-S53/A4S00 , SAI143-S53/A4S10 , SAI143-S53/A4D00 , SAI143-S53/A4D10 ,SAI143-S53/PRP, SAI143-S53/CCC01
SAI143-S63/A4S00 , SAI143-S63/A4S10 , SAI143-S63/A4D00 , SAI143-S63/A4D10 ,SAI143-S63/PRP, SAI143-S63/CCC01
SAI143-SE3/A4S00 , SAI143-SE3/A4S10 , SAI143-SE3/A4D00 , SAI143-SE3/A4D10 ,SAI143-SE3/PRP, SAI143-SE3/CCC01
SAI143-SF3/A4S00 , SAI143-SF3/A4S10 , SAI143-SF3/A4D00 , SAI143-SF3/A4D10 ,SAI143-SF3/PRP, SAI143-SF3/CCC01
SAI143-S5C/A4S00 , SAI143-S5C/A4S10 , SAI143-S5C/A4D00 , SAI143-S5C/A4D10 ,SAI143-S5C/PRP, SAI143-S5C/CCC01
SAI143-S6C/A4S00 , SAI143-S6C/A4S10 , SAI143-S6C/A4D00 , SAI143-S6C/A4D10 ,SAI143-S6C/PRP, SAI143-S6C/CCC01
SAI143-SEC/A4S00 , SAI143-SEC/A4S10 , SAI143-SEC/A4D00 , SAI143-SEC/A4D10 ,SAI143-SEC/PRP, SAI143-SEC/CCC01
SAI143-SFC/A4S00 , SAI143-SFC/A4S10 , SAI143-SFC/A4D00 , SAI143-SFC/A4D10 ,SAI143-SFC/PRP, SAI143-SFC/CCC01
YOKOGAWA ESD Analog Input Module SAI143-H53