MTL5511 1 channel output safe isolator 100% original product-hkxytech
  • MTL5511 1 channel output safe isolator 100% original product

MTL5511 1 channel output safe isolator 100% original product

2017-12-08 11:06:52

Description:

MTL5500 series isolated barrier……

Notice:

New Products

Siemens 6DR5220-0EG00-0AA0 SIPART PS2 smart electropneumatic positioner for pneumatic linear and actuators

SIPART PS2 smart electropneumatic positioner for pneumatic linear and part-turn actuators; 2-,3-,4-wire; 4...20mA with HART-interface; double action; polycarbonate enclosure with fixable slipping clutch with explosion protection (ATEX/IECEx/FM/CSA); Intrinsic safety Connection thread el.: M20x1.5 / pneu.: G 1/4 without limit monitor without option module . Brief instructions German / English / Chinese . without mounted pressure gauge block

Allen-Bradley 2711P-T12C4D8 PanelView Plus 6 Graphic Terminals Operator Interfaces Rockwell Automation

Provides significant improvements over the PanelView Plus 400 graphic terminals

Siemens 7MF4033-1BA10-2AB6 SITRANS transmitter

SITRANS P DS III / P410, HART,4-20 mA transmitter for pressure Measuring cell filling silicone oil, normal cleaning Span: 0,01 ... 1 bar g (0.15 ... 14.5 psi g), overload limit 6 bar Diaphragm stainless steel, measuring cell stainless steel Female thread 1/2-14 NPT Die-cast aluminium housing International design english inscription and documentation as cd None explosion protection Electric connection and cable inlet: cable gland M20 x 1.5 Housing cover with window

Assortments

Description

Production overviews


MTL 5500 Intrinsically Safe Isolators  MTL5511

296768965832147148.jpg

MTL5511 product specification
Number of channels: One
Location of switches
Zone 0, IIC, T6 hazardous area Div. 1, Group A hazardous
location Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected) 
User-selectable via switches on the side of the unit. A line fault is indicated by an LED. The channel output relay is de-energised if an input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input 500Ω to 1kΩ in series with switch 20kΩ to 25kΩ in parallel with switch
Safe-area output 
Single pole relay with changeover contacts Note: reactive loads must be adequately suppressed
LED indicators 
Green: power indication
Yellow: channel status, on when output energised
Red: LFD indication, on when line fault detected
Maximum current consumption
 25mA at 24V
Power dissipation within unit :0.6W at 24V
Safety description (each channel) Uo=10.5V Io=14mA Po=37mW Um = 253V rms or dc

If you need any other information for MTL5500 series isolated barrier, please feel free to contact me.

Contact details

HONGKONG XIEYUAN TECH CO., LIMITED

Telephone:86-027-85880977

Mobile :86-13545206420(Whatapp&Wechat is available)

Fax:86-027-85309780

Skype:Diana@hkxytech.com

E-mail:Diana@hkxytech.com

Website:www.hkxy-lowvoltage.com