MTL5511 1 channel output safe isolator 100% original product-hkxytech
  • MTL5511 1 channel output safe isolator 100% original product

MTL5511 1 channel output safe isolator 100% original product

2017-12-08 11:06:52

Description:

MTL5500 series isolated barrier……

Notice:

New Products

Honeywell Analytics SPSTAXH1SS Sensepoint Flammable and Toxic Gas Detector Explosion-Proof Transmitters

Cost-effective, fixed point gas detector for the protection of personnel and plant from flammable, toxic and Oxygen gas hazards

Honeywell Analytics Sensepoint XCD RTD Remote toxic and oxygen gas detector for industrial applications

3 wire, 4-20mA and RS485 MODBUS output fixed point detector with in-built alarm and fault relays for the protection of personnel and plant from toxic and oxygen hazards.

Honeywell Analytics Sensepoint XCD RFD Remote Flammable Gas Monitor Explosion-Proof Transmitters

3-wire, 4-20mA, transmitter with optional Modbus for use with remotely mounted flammable gas sensors 705 and 705HT

Assortments

Description

Production overviews


MTL 5500 Intrinsically Safe Isolators  MTL5511

296768965832147148.jpg

MTL5511 product specification
Number of channels: One
Location of switches
Zone 0, IIC, T6 hazardous area Div. 1, Group A hazardous
location Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected) 
User-selectable via switches on the side of the unit. A line fault is indicated by an LED. The channel output relay is de-energised if an input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input 500Ω to 1kΩ in series with switch 20kΩ to 25kΩ in parallel with switch
Safe-area output 
Single pole relay with changeover contacts Note: reactive loads must be adequately suppressed
LED indicators 
Green: power indication
Yellow: channel status, on when output energised
Red: LFD indication, on when line fault detected
Maximum current consumption
 25mA at 24V
Power dissipation within unit :0.6W at 24V
Safety description (each channel) Uo=10.5V Io=14mA Po=37mW Um = 253V rms or dc