Top Industrial Automation and Electrical Instrument from HKXYTECH
  • Eaton MTL4575-MTL5575 Temperature Converter MTL Intrinsic Safety Intrinsically Safe Isolators MTL5500 range
  • Eaton MTL4575-MTL5575 Temperature Converter MTL Intrinsic Safety Intrinsically Safe Isolators MTL5500 range

Eaton MTL4575-MTL5575 Temperature Converter MTL Intrinsic Safety Intrinsically Safe Isolators MTL5500 range

2018-07-04 16:51:41

Description:

1ch Temperature converter, RTD / THC with alarm……

New Products

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0DH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature New load group, width: 22.5 mm.

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA

Siemens 6DL1193-6TP00-0BH1 SIMATIC ET 200SP HA, Terminal block, Type H1, 32 push-in terminals, internal reference temperature Width: 22.5 mm.

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GC00-0NN0 SIMATIC ET 200SP HA, carrier module 8-fold carrier for holding 8 I/O modules of the ET 200SP HA.

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA

Siemens 6DL1193-6GA00-0NN0 SIMATIC ET 200SP HA, carrier module 2-fold carrier for holding 2 I/O modules of the ET 200SP HA.

Assortments

Description

Eaton MTL4575-MTL5575 Temperature Converter THC or RTD input+Alarm MTL Intrinsic Safety Intrinsically Safe Isolators MTL5500 range

 

1ch Temperature converter, RTD / THC with alarm

 

Similar Types : MTL5018AC, MTL5501-SR, MTL5510, MTL5510B, MTL5511, MTL5513, MTL5514, MTL5514D, MTL5516C, MTL5517, MTL5521, MTL5522, MTL5523, MTL5523V-VL, MTL5524, MTL5525, MTL5526, MTL5541, MTL5541A, MTL5541AS, MTL5541S, MTL5544,  MTL5544A, MTL5544AS, MTL5544D, MTL5544S, MTL5546, MTL5546Y, MTL5549, MTL5549Y,  MTL5573, MTL5575, MTL5576-RTD, MTL5576-THC, MTL5581, MTL5582, MTL5582B, MTL5531, MTL5532, MTL5561, MPA5500, MTL5051, MTL5053, MTL5314, MTL5599, PSG60E24RM (replaces MTL5991)

 

The MTLx575 converts a low-level dc signal from a temperature sensor mounted in a hazardous area into a 4/20mA current for driving a safearea load. Software selectable features include linearisation, ranging, monitoring, testing and tagging for all thermocouple types and 2-, 3- or 4-wire RTDs. (For thermocouple applications the HAZ-CJC plug on terminals 1–3 includes an integral CJC sensor). Configuration is carried out using a personal computer. A single alarm output is provided and may be configured for process alarm or to provide notice of early thermocouple failure.

 

SPECIFICATION

 

Number of channels

One

 

Signal source

THC types J, K, T, E, R, S, B or N to BS 60584 and XK mV input

RTDs 2/3/4-wire platinum to BS 60751

Pt 100, Pt 500, Pt 1000

Cu-50 & Cu-53

Ni 100/500/1000 DIN 43760

 

Location of signal source

Zone 0, IIC, T4-6 hazardous area

Division 1, Group A, hazardous location

 

Input signal range

–75 to +75mV, or 0 to 400Ω (0 to 1000Ω Pt & Ni sensors)

 

Input signal span

3 to 150mV, or 10 to 400Ω (10 to 1000Ω Pt & Ni sensors)

 

RTD excitation current

200µA nominal

 

Cold junction compensation

Automatic or selectable

 

Cold junction compensation error

≤ 1.0°C

 

Common mode rejection

120dB for 240V at 50Hz or 60Hz (500ms response)

 

Series mode rejection

40dB for 50Hz or 60Hz

 

Calibration accuracy (at 20°C)(includes hysteresis, non-linearity and repeatability)

Inputs: (500ms response)

mV/THC: ± 15µV or ± 0.05% of input value

(whichever is greater)

RTD: ± 80mΩ

Output: ± 11µA

 

Temperature drift (typical)

Inputs:

mV/THC: ± 0.003% of input value/°C

RTD: ± 7mΩ/°C

Output: ± 0.6µA/°C

 

Example of calibration accuracy and temperature drift(RTD input - 500ms response)

Span: 250Ω

Accuracy: ± (0.08/250 + 11/16000) x 100%

= 0.1% of span

Temperature drift: ± (0.007/250 x 16000 + 0.6) µA/°C

= ±1.0µA/°C

 

Safety drive on sensor failure

Upscale, downscale, or off

 

Early burnout

Early burnout detection for thermocouples (when selected)

Alarm trips when loop resistance increase is > 50Ω

 

Output range

4 to 20mA nominal into 600Ω max.

 

Alarm output (configurable)

Relay ON in alarm, 250mA @ 35V max

 

Maximum lead resistance (THC)

600Ω

 

Response time

Configurable - 500 ms default

(Accuracy at 100/200ms - contact MTL)

 

LED indicator

Green: power and status indication

Yellow: alarm indication, on when contacts are closed

 

Maximum current consumption (with 20mA signal)

50mA at 24V

 

Power dissipation within unit (with 20mA signal)

1.2W at 24V

 

Safety description

Refer to certificate for parameters. Um=253V rms or dc

 

Configurator

A personal computer running MTL PCS45 software with a

PCL45USB serial interface.

 

If you have any question, please do not hesitate to contact with me online

Contact details :

Shirley Sun

Sales Engineer

HONGKONG XIEYUAN TECH CO., LIMITED

Add : 7-A16, Caishen Commercial Plaza, Hangkou Railway Station, Wuhan, China

M : +86-15172506760 (WhatsApp & Wechat) | T : +86-27-85309780  | F : +86-27-85309780

Email : Shirley@whxyauto.com     Skype : 169649423@qq.com

Web : www.hkxytech.com