The MTLx521 and the MTL4521L are loop-powered modules which enable a device located in the hazardous area to be controlled from the safe area. They can all drive a certified intrinsically safe low-power load, as well as non-energy-storing simple apparatus such as an LED.……

New Products

OMRON CS1W-CN133 CS1 I/O Connecting Cable

OMRON CS1W-CN133 CS1 I/O Connecting Cable. Connects CS1 Expansion I/O Backplanes to CPU Backplanes or other CS1 Expansion I/O Backplanes.

OMRON CS1W-AD041-V1 CS1W series Analog Input Unit

OMRON CS1W-AD041-V1 CS1W series Analog Input Unit. Contact us to learn more about the OMRON CS1G/CS1H/CS1W/CS1D SYSMAC CS1 Programmable Controller.

OMRON CS1H-CPU63H CS1H CPU Unit

OMRON CS1H-CPU63H CS1H CPU Unit. Omron CS1 Series is widely used in industrial automation applications such as production line control, process monitoring, packaging, material handling, and power plant systems.

OMRON CS1G-CPU42H CS1G CPU Unit

OMRON CS1G-CPU42H CS1G CPU Unit. Ideal for control of power generators, water supply utilities, 24/7 production.

Assortments

Description

Eaton MTL4521/L-MTL5521 MTL Intrinsically Safety Intrinsically Safe Isolators MTL 5500 range

Loop powered solenoid driver, IIC

 

Solenoid/ Alarm Driver loop-powered, IIC

 

Similar Types : MTL5018AC, MTL5501-SR, MTL5510, MTL5510B, MTL5511, MTL5513, MTL5514, MTL5514D, MTL5516C, MTL5517, MTL5521, MTL5522, MTL5523, MTL5523V-VL, MTL5524, MTL5525, MTL5526, MTL5541, MTL5541A, MTL5541AS, MTL5541S, MTL5544,  MTL5544A, MTL5544AS, MTL5544D, MTL5544S, MTL5546, MTL5546Y, MTL5549, MTL5549Y,  MTL5573, MTL5575, MTL5576-RTD, MTL5576-THC, MTL5581, MTL5582, MTL5582B, MTL5531, MTL5532, MTL5561, MPA5500, MTL5051, MTL5053, MTL5314, MTL5599, PSG60E24RM (replaces MTL5991)

 

The MTLx521 and the MTL4521L are loop-powered modules which enable a device located in the hazardous area to be controlled from the safe area. They can all drive a certified intrinsically safe low-power load, as well as non-energy-storing simple apparatus such as an LED.

 

Number of channels

One

 

Location of load

Zone 0, IIC, T46 hazardous area if suitably certified

Div. 1, Group A hazardous location

 

Input voltage

20 to 35V dc

 

Hazardous-area output (MTLx521)

Minimum output voltage: 13.6V at 48mA

Maximum output voltage: 24V from 180

Current limit: 48mA minimum

 

Hazardous-area output (MTL4521L)

Minimum output voltage: 11.1V at 48mA

Maximum output voltage: 24V from 232

Current limit: 48mA minimum

 

Output ripple

< 0.5% of maximum output, peak to peak

 

Response time

Output within 10% of final value within 100ms

 

LED indicator

Yellow: output status, on when output active

 

Maximum current consumption

90mA at 24V

 

Power dissipation within unit

1.4W at 24V

 

Safety description (MTLx521)

Uo=25V Io=147mA Po=0.92W Um = 253V rms or dc

 

Safety description (MTL4521L)

Uo= 25V Io= 108mA Po= 0.68W Um = 253V rms or dc

 

If you have any question, please do not hesitate to contact with me online

Contact details :

Shirley Sun

Sales Engineer

HONGKONG XIEYUAN TECH CO., LIMITED

Add : 7-A16, Caishen Commercial Plaza, Hangkou Railway Station, Wuhan, China

M : +86-15172506760 (WhatsApp & Wechat) | T : +86-27-85309780  | F : +86-27-85309780

Email : Shirley@whxyauto.com     Skype : 169649423@qq.com

Web : www.hkxytech.com