MTL5511 1 channel output safe isolator 100% original product
2017-12-08 11:06:52
Description:
MTL5500 series isolated barrier……
New Products
Orbinox VG SERIES 61 Slurry knife gate valve
Orbinox SERIES 61 (VG) model knife gate valve is a wafer type valve equipped with two metal reinforced rubber sleeves,designed for applications with abrasive slurries.
Crosby J-Series Direct Spring Pressure Relief Valves
J-Series valves provide high quality and dependable overpressure protection for air, gas, steam, vapor, liquid and two-phase applications in one simple design. Now available with two new to the world technologies, Balanced Diaphragm and Bellows Leak Detection.
Vanessa Series 30,000 Cryogenic Triple Offset Valve
The Vanessa Series 30,000 Cryogenic Triple Offset Valve is a virtually maintenance-free valve with tightness, operability and torque demand unaffected by cryogenic conditions and severe temperature fluctuations.
Sempell Model SOT High pressure steam safety valve
The Sempell Model SOT is a high-pressure steam safety valve designed for boiler protection and steam system safety.
Assortments
Description
Production overviews
MTL 5500 Intrinsically Safe Isolators MTL5511
MTL5511 product specification
Number of channels: One
Location of switches
Zone 0, IIC, T6 hazardous area Div. 1, Group A hazardous
location Location of proximity detector
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Hazardous-area inputs
Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Voltage applied to sensor
7 to 9V dc from 1kΩ ±10%
Input/output characteristics
Normal phase Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
Hysteresis: 200µA (650Ω) nominal
Line fault detection (LFD) (when selected)
User-selectable via switches on the side of the unit. A line fault is indicated by an LED. The channel output relay is de-energised if an input line fault is detected.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Note: Resistors must be fitted when using the LFD facility with a contact input 500Ω to 1kΩ in series with switch 20kΩ to 25kΩ in parallel with switch
Safe-area output
Single pole relay with changeover contacts Note: reactive loads must be adequately suppressed
LED indicators
Green: power indication
Yellow: channel status, on when output energised
Red: LFD indication, on when line fault detected
Maximum current consumption
25mA at 24V
Power dissipation within unit :0.6W at 24V
Safety description (each channel) Uo=10.5V Io=14mA Po=37mW Um = 253V rms or dc