Top Industrial Automation and Electrical Instrument from HKXYTECH

Pepperl+Fuchs Switch Amplifier KFD2-SH-Ex1, 1-channel isolated barrier, 24 V DC supply, Line fault detection.

The device transfers digital signals (SN/S1N proximity sensors or approved dry contacts) from a hazardous area to a safe area. The input controls one relay contact output with 3 NO contacts (one output is in series to the both output relays for the safety function), one relay contact output with one NO contact, and one passive transistor output. Unlike an SN/S1N series proximity sensor, a mechanical contact, requires a 10 kΩ resistor to be placed across the contact in addition to a 1.5 kΩ resistor in series. Lead breakage (LB) and short circuit (SC) conditions of the control circuit are continuously monitored. During an fault condition, the fault indication output energizes and outputs I and II de-energize. For safety applications up to SIL3, output I must be used. For safety applications up to SIL2, output I and output II can be used.


Associated Products: KFD2-SH-Ex1

KFD2-EB2

UPR-03

UPR-03-M

UPR-03-S

K-DUCT-BU

K-DUCT-BU-UPR-03


Accessories:

KF-ST-5GN

KF-ST-5BU

KF-CP

 


If you have any questions, please contact online or email to info@hkxytech.com Contact our sales manager by email.
Click here to see more
products →

Other news